Air Cooled Scroll Chillers
Modular Air Cooled Chillers
- Capacity Range: 65kW(18.5Tons), 132kW(37.5Tons);
- Refrigerant: R-410A
- Compressor Design: Hermetic Scroll Compressor, Copeland/Panasonic.
- Refrigerant Circuits: dual circuits
- Energy Efficiency Rating (EER):10.9, COP 3.2
- Power Supply: 380~415V/3PH/50Hz
- Optional partial heat recovery and full heat recovery
- 描述
- Specifications
- Structure Drawing
- Global Tab
Air Cooled Scroll Chillers are highly energy-efficient and perfectly designed in a compact size, especially suitable for air conditioning system of small buildings, factories, retrofit applications. These chillers are operation friendly, easy for installation and maintenance. Within multiple compressors configuration, each compressor is supported by an individual and separate refrigeration circuit. The separate refrigeration circuit makes the servicing of under-maintenance modules easy, simultaneous to the working module being on duty.
Air Cooled Scroll Chiller | |||||||||||
Model | LAWC-05F/T | LAWC-08F/T | LAWC-10F/T | LAWC-12.5F/T | LAWC-15F/T | ||||||
Refrigerant | R407C | R134a | R407C | R134a | R407C | R134a | R407C | R134a | R407C | R134a | |
Cooling Cap. | kW | 12.8 | 9.5 | 20.8 | 15.3 | 27.2 | 20 | 31.4 | 23.2 | 39.5 | 29.1 |
Tons | 3.6 | 2.7 | 5.9 | 4.3 | 7.7 | 5.7 | 8.9 | 6.6 | 11.2 | 8.3 | |
Input Power | kW | 4.1 | 2.9 | 6.95 | 4.95 | 8.7 | 6.2 | 9.7 | 7 | 13 | 9.2 |
Operation Current A | 8.7 | 6 | 12.8 | 8.7 | 16.7 | 11.5 | 18.3 | 12.5 | 25.3 | 17.3 | |
Power Supply | 380V /3PH /50Hz | ||||||||||
Safety Devices | Reverse phase protection, phase loss protection, overcurrent protection, discharge temperature protection, high and low pressure protection, low-temperature protection, water flow protection | ||||||||||
Compressor | Power input kW | 3.8 | 2.6 | 6 | 4.1 | 7.6 | 5.1 | 8.6 | 5.9 | 11.9 | 8.1 |
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Refrigerant Circuits | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Capacity Control % | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | 0,100 | |
Air side heat exchanger | Type | Copper tubes with hydrophilic corrugated aluminum fins | |||||||||
Fan motor power kW | 0.24 | 0.65 | 1.13 | 1.13 | 1.85 | ||||||
Fan qty | 1 | 1 | 1 | 1 | 1 | ||||||
Water side heat exchanger | Type | Shell and Tube | |||||||||
Maximum pressure MPa | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
IN/OUT pipe inch | 1 1/2" | 1 1/2" | 1 1/2" | 2" | 2" | ||||||
CW IN/OUT Temp. ℃ | 12/7 | 12/7 | 12/7 | 12/7 | 12/7 | ||||||
Water flow L/min | 37 | 27.0 | 60.0 | 44.0 | 78.0 | 57.0 | 90.0 | 66.0 | 113.0 | 83.0 | |
Pressure Drop KPa | 17 | 29 | 34 | 40 | 43 | ||||||
Operation Noise dB(A) | 64 | 57 | 66 | 59 | 69 | 61 | 69 | 61 | 70 | 63 | |
Unit Weight(kg) | 180 | 300 | 360 | 410 | 480 | ||||||
Unit dimensions(L*W*H) | 1050*800*1150 | 1050*1040*1750 | 1050*1040*1750 | 1200*1040*1750 | 1250*1100*1750 | ||||||
Note: The above data are gotten under the following testing conditions: | |||||||||||
1. Nominal cooling capacity: ambient air DB/WB 35℃/24℃,inlet/outlet chilled water 12/7℃, fouling factor 0.088 m2 .℃/kW; | |||||||||||
2. Chilled water range 5~15℃, 5~20℃( R134a ), ambient temperature 15~43℃, 20~50℃(R134a); | |||||||||||
3. The specifications may have some changes due to product improvement without notice. |
Modular Air Cooled Scroll Chiller 132kW