Industrial Water Cooled Liquid Chiller (30~600RT)

Industrial Water Cooled Liquid Chiller (30~600RT)

  1. Easy Installation & Maintenance

◆Chiller unit, cooling water pump, chilled water pump, water tank, water pipe, valves and controller can be built in one common chassis unit;

  1. Cost saving

System unit electrical components and controller are centralized in a single central control cabinet. So, it lessen control boxes and systems are more reliable.

Packaged construction, less occupied space, flexible placement.

  1. High Efficiency

Highest COP up to 6.0 Optional heat recovery unit, H’Stars’s patent product Recoverable heat is 30-80% of the rated cooling capacity, supplying free hot water up to 70℃. COP is increased by 5% with heat recovery option.

4.Reliability and Stability

◆Main components: the evaporator and condenser are produced by the H’Stars, by optimized component matching software Double refrigerant circuits design with standby capacity 7 protection devices With National Test Laboratory to test unit for performance and quality assurance

  1. Intelligent Control

◆Adopting MCU or PLC, Remote control available,BMS compatible with Rs485

  • Description
  • Specifications
  • Structure
  • Global Tab

All industrial chillers are designed and manufactured for industrial application, there are 52 models of standard configuration, cooling capacity ranges from 120kW~9699kW, making chilled water from 5~20℃. Industrial chillers can meet different industrial requirements like pharmaceutical industry, chemical industry, plastic injection&plastic extruder, beverage industry, milk collection, clean room,etc.

Features and Benefits

  1. Easy Installation & Maintenance

◆Chiller unit, cooling water pump, chilled water pump, water tank, water pipe, valves and controller are optional to built in one common chassis unit; Easy to install and check Control board alarm provides fast system trouble-shooting Compact size, lesser footprint, flexibility for positioning

Control UI shows error information directly, convenient and timely report for fast troubleshooting.

  1. Cost saving

System unit electrical components and controller are centralized in a single central control cabinet. So, it lessens control boxes and systems are more reliable.

Packaged construction, less occupied space, flexible placement.

3. High Efficiency

Highest COP up to 6.0 Optional heat recovery unit, H’Stars’s patent product Recoverable heat is 30-80% of the rated cooling capacity, supplying free hot water up to 70℃. COP is increased by 5% with heat recovery option.

4.Reliability and Stability

◆Main components: the evaporator and condenser are produced by the H’Stars, by optimized component matching software Double refrigerant circuits design with standby capacity 7 protection devices With National Test Laboratory to test unit for performance and quality assurance

5.Intelligent Control

◆Adopting MCU or PLC, Remote control available,BMS compatible with Rs485

6. Non-standard configuration units available

◆Flexible design on the size and structure for easy transportation and assembling to save installation time and commission test time Various refrigerant available, R22, R407c,R134a.

Special function unit available: explosive-proof, anti-corrosive-proof

 Standard Power supply: 380~415V/3PH/50Hz, Optional 440V/3PH/60Hz, 460v/3ph/60Hz, 220V/3PH/60Hz.

   Industrial Water Cooled Liquid Chiller 

40STD Industrial Water Cooled Screw Chiller
Model  40STD370WSI430WSI460WSI510WSI610WSI
RefrigerantR22R407CR22R407CR22R407CR22R407CR22R407C
Rated Cooling

Cap.

×1000 kcal/h317.9310.2367.5358.5397.8391.8438.0422.9521.2500.4
kW370361427417463456509492606582
USRT105.1102.6121.5118.5131.5129.6144.8139.8172.3165.5
Input PowerkW65.863.176.173.683.180.592.488.2107.3102.3
Comp.power kW×Qty65.8×163.1×176.1×173.6×183.1×180.5×192.4×188.2×1107.3×1102.3×1
Operation Current  A110.6106.1128.0123.8139.7135.4155.3148.3180.3171.9
Power Supply3φ-380V-50Hz
Safety DevicesPhase reverse protection, lack phase protection,over current protection,

discharge temperature protection, high and low pressure protection, low

temperature protection, water flow protection,etc

Refrigerant Circuits11111
Energy Control  %0,50,75,100
Refrigerant Charge  kg5259657186
Condenser Shell-and-Tube Type
Water Side Max Pressure Mpa1
Condenser Inlet/Outlet

Pipe Size  inch

4″4″4″5″5″
Cooled Water Flow  m3/h74.972.986.684.493.892.2103.599.7122.7117.7
Condenser Press.Drop KPa52525050505050505151
Evaporator Shell-and-Tube Type
Water Side Max Pressure Mpa1
Evaporator Inlet/Outlet

Pipe Size  inch

3″4″4″4″4″
Chilled Water Flow  m3/h63.662.073.571.779.678.487.684.6104.2100.1
Evaporator Press.

Drop KPa

55556161666663634343
Noise Level  dB(A)75.075.075.075.075.0
Unit Weight kg15101620173018302140
Running Weight kg16701780187020202400
Note:
1.Rated Cooling capacity:Evaporator inlet/out water temperature 17℃/12℃,Condenser inlet/outlet water temperature 30/35℃; fouling factor 0.088㎡·℃/kW;
2.Chilled water temperature range:5-20℃;
3. Cooled water  temperature:15~40℃;
4.Due to improvement,Specifications and dimensions may be changed without notice.

 

   ModelABCDEFGHI
40STD-510WSI329501150180022008402501852100827
40STD-610WSI330001200195022009202501852100878

 

Online Service